Snow Load Checks Before Ordering Ground-Mount PV Racking

A module datasheet may show a front load rating while the project drawing calls for a different support layout from the one tested. Before ordering racking for a snowy site, compare the load assumptions, mounting details and ground clearance on the same set of drawings.

Ask the designer for the loads at the array

Record the governing design criteria and the load cases the designer has evaluated for each rack configuration. Ask how the design treats uneven accumulation, snow sliding toward the lower edge and applicable load combinations. The U.S. Department of Energy notes that snow can collect unevenly along the lower edge of tilted modules, increasing stress in that area. [1]

Match the module rating to the proposed attachments

Request the installation manual for the exact module model and identify the applicable mounting diagram. Compare its support orientation, attachment positions and number of supports with the rack drawings. Ask the reviewer to confirm how the published test or design load relates to the project demand. Record the manual revision and drawing number in the procurement file. [1]

Check where shed snow will collect

Mark the lowest module edge on the grading plan. Review the expected accumulation below it and the space available for shed snow beside roads and service aisles. DOE guidance identifies a trade-off between raising the array for snow clearance and increasing wind loading. Route changes in rack height or tilt back to the structural designer before they enter the purchase order. [1]

Release the order with a record crews can use

  • List the accepted module model, drawing revisions and mounting detail for each rack type.
  • Identify rows where the approved clearance or support detail differs from the typical drawing.
  • At the first assembly, compare the actual support locations and lower edge elevation with the approved drawings.
  • Send substitutions and field deviations for review before repeating the affected detail.

Keep the site load review, module mounting diagram and racking drawings together. That package lets procurement check the quoted configuration and gives installers a specific detail to verify in the field.

Sources

  1. U.S. Department of Energy FEMP — Solar Photovoltaic Hardening for Resilience in Winter Weather

Similar Posts

Leave a Reply

Your email address will not be published. Required fields are marked *